Reimers designs and builds many models of HLR hot water systems. All are designed and built in accordance with requirements of the ASME Boiler and Pressure Vessel Code and ASME CSD-1. The model series shown conforms to the following specifications.
Maximum pressure 100psi • Maximum temperature 250°F • Each boiler bears the National Board Stamp “H” • Shell fiberglass insulation thickness minimum 1.5” • Power range 15kW - 105kW with up to 8 heating stages, depending on model • Heating stages controlled by Honeywell T775 series boiler controller.
Standard features include: A.S.M.E. pressure relief valve • One (1) primary high temperature cutoff control with automatic reset and one (1) secondary high temperature cutoff control with manual reset • One (1) low water cutoff control with manual reset • PID-step controller with number of heating stages depending on the boiler heating power • Digital readout of the operating temperature • Magnetic contactors • Internal branch circuit fusing • Main supply power distribution block • Indicator lights for POWER, HEATING, CIRCULATOR PUMP and ALARMS • Pressure and temperature gauge