MANUFACTURING QUALITY STEAM PRODUCTS FOR 100 YEARS
Specifications and Dimensions <<<< Previous Page <<<<
Model HMH 25E1B
MODEL CAPACITY
BTUH
OUT PUT
(KW)
NO. and
SIZE of
ELEMENTS
VOLTS AMPS MINIMUM
WIRE SIZE
INLET &
OUTLET SIZE
FLOW 20° F
RISE G.P.M.
WATER
CAP. GAL. BOILER
SQUARE FT.
OF
RADIATION
DIMENSIONS
LESS TANK
W-H-L
INCHES
APPROX.
SHIPPING
WEIGHT
HM-12 40535 (12) 2-4.5 KW
1-3 KW
240 50 NO.6 1 1/4 4.1 7 270 22 X 25 X 35 305
HM-15 50668 (15) 3-5 KW 240 63 NO.6 1 1/4 5.1 7 338 22 X 25 X 35 305
HM-18 60802 (18) 4-4.5 KW 240 75 NO.4 1 1/4 6.1 7 405 22 X 25 X 35 308
HM-20 67558 (20) 4-5 KW 240 84 NO.4 1 1/4 6.8 7 450 22 X 25 X 35 308
HM-22 76002 (22.5) 5-4.5 KW 240 94 NO.2 1 1/4 7.7 7 507 22 X 25 X 35 311
HM-25 84447 (25) 5-5 KW L 240 105 NO.2 1 1/4 8.5 7 563 22 X 25 X 35 311

Model "HM" - Boiler Only
Model "HMH" - Boiler with Circulating Package (pump, air eliminator, expansion tank, automatic air vent, automatic fill valve and room thermostat)

Convenient Location
Place our electric boiler adjacent to the application. Oil or gas fired boilers require a separate boiler room.

Dryer Steam
Our electric boilers provide dry, saturated steam. Oil or gas fired boilers often require long steam lines which result in excessive condensation.

Economical Installation
Electrical wiring is less expensive to run than steam piping. Not having a separate boiler room or vented exhaust saves money.

Safer Operation
Electric boilers are flameless and safer. This eliminates the risk of flareback, firebox explosions and smoke damage.

 

Quality Excellence
- U.L. Listed
- Bears National Board Boiler Stamp
- Built in accordance with ASME code
- A.S.M.E. CSD-1
- C.S.A. & C.R.N. Available for Canada

Factory Assurance
- 1 Year Parts Warranty
- Easy Installation
- Two Week Delivery on Most models
- Sizes ranging from 1.5 to 500 KW (.15 to 50 B/H.P.)
- USA Voltages (208, 240, 480, 600 Volts)
- Foreign Voltages (220, 346, 380, 415 Volts)

Customer Options
- Condensate return Systems
- Blowdown Systems
- Stainless Steel Models up to 12 B.H.P.

 

Reimers Electra Steam
P.O. Box 37
4407 Martinsburg Pike · Clear Brook, Virginia 22624
Phone: 540-662-3811 · Fax: 540-665-8101
Toll Free: 1-800-872-7562
Fax-Free: 1-800-726-4215
E-mail: sales@reimersinc.com
 Live chat by LivePerson

About Reimers | Steam Applications | Steam Boilers & Steam Generators | Hot Water Boilers | Specifications & Dimensions
Steam Tips: News and Information | Stainless Steel Boilers | Frequently Asked Questions | Contact Reimers | Product Videos
Manuals | Home | Site Map

© 2007 Reimers Electra Steam, Incorporated